Explicit Messaging Chapter 5

Follow these steps to configure a message.

1. Choose the appropriate parameters in the Message Configuration window.

Parameter

Choice

Message Type

Choose message type CIP Generic.

Service Type

Read: Select service type Get Attribute Single
Write: Select service type Set Attribute Single

Instance

Refer to

Appendix A

for the CIP Instance of the data table you are requesting to

read. In this example, the power monitor’s Voltage, Amp, and Frequency data

table is instance 14.

Class

4

Attribute

3

Destination

Get Attribute Single - This is the controller tag in which to store the data being

read.

Source Element

Set Attribute Single - Refer to

Appendix A

for the address of the specific data

table address you’re writing to.

Source Length

Set Attribute Single - This is the number of elements of the source element, to

be written to the power monitor.