Chapter 5 Explicit Messaging

RSLogix5000 – Message Configuration Using PLC5 or SLC Typed

Read/Write

This is an example of how to set up a message instruction to read or write single

or multiple elements from a power monitor using PLC5 or SLC Typed messages.

This setup applies to ControlLogix and CompactLogix programmable logic

controllers.

Table 2 - Message Type

Read/Write Type

Communication

Read/Write Message Type

Single Element

Serial

SLC Typed

Single Element

Ethernet

PLC5 Typed or SLC Typed

Multiple Element

Serial

SLC Typed

Multiple Element

Ethernet

PLC5 Typed or SLC Typed or CIP Generic

(1)

(1) The CIP Generic message type is only available for RSLogix5000 software. All elements in the data table are written to or read back.