Metered parameters, Setup – Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 33

Advertising
background image

Rockwell Automation Publication 1408-UM001D-EN-P - September 2013

33

PowerMonitor 1000 Unit Features Chapter 2

Metered Parameters

The power monitor calculates and returns the following demand values:

Real power demand, kW

Reactive power demand, kVAR

Apparent power demand, kVA

Demand power factor, percent lagging (-) or leading (+)

Projected kW, kVAR, and kVA demand

Demand interval elapsed time, minutes

Projected demand calculates a linear projection of demand at the end of a demand

interval.

Demand power factor is calculated using the following formula.

kW Demand / kVA Demand

Setup

Demand metering requires basic analog input setup as well as demand calculation

setup. Basic demand set-up parameters are found in the Advanced Setup menu.

Network demand synchronization is available on units connected to an Ethernet

network. Network-demand synchronization set-up parameters are found in the

Ethernet communication set-up menu.

Parameter

Description

Range

Default

User

Setting

Demand Source

(advanced setup)

Selects the source of the demand end-of-interval (EOI) signal.
0 = Internal Timer

1 = Status Input 2

2 = Controller Command

3 = Ethernet Demand Broadcast

Network-demand synch options are available only on units with an optional Ethernet

network installed.

If Demand Broadcast Master Select is set to master then a Demand Source value

of 0…2 selects the EOI source that is used to trigger the demand-synch master

broadcast.

If Demand Broadcast Master Select is set to slave then a Demand Source value of

0…3 selects the EOI source.

0…3

0

Demand Period

Length (advanced

setup)

Specifies the period for demand calculations. The following include special cases.
Demand source = 0 (internal time) and demand period length = 0 then demand

metering is disabled
Demand source 0 and demand period length = 0 then projected demand is disabled
Demand source 0 and demand period length 0 then projected demand is calculated

using the unit’s internal clock

0…99 min

15 min

Number of

Demand Periods

(advanced setup)

Specifies the number of demand periods to average together for demand

measurement. This parameter is used for sliding window demand calculations. For

example, for a 30 minute sliding-window, demand period length = 2 minutes and

number of demand periods = 15.

1…15

1