Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 111

Advertising
background image

Rockwell Automation Publication 1408-UM001D-EN-P - September 2013

111

PowerMonitor 1000 Data Tables Appendix A

Table 59 - User-configurable Table Setup Parameters

CSP File No.

N44

CIP Instance

29

Applies to

EM3 only

No. of Elements

17

No. of Words

17

Data Type

Integer

Data Access

Read/Write

Table 60 - User-configured Table Setup

Element

No.

Modbus

Address

Element Name

Default Value

Range

Description

0

41001

Password

0

0…9999

Required for configuration,

returns -1.

1

41002

Selection for Parameter #1

29 (L1 Current)

0…110

2

41003

Selection for Parameter #2

30 (L2 Current)

3

41004

Selection for Parameter #3

31 (L3 Current)

4

41005

Selection for Parameter #4

37 (L1-L2 Voltage)

5

41006

Selection for Parameter #5

38 (L2-L3 Voltage)

6

41007

Selection for Parameter #6

39 (L3-L1 Voltage)

7

41008

Selection for Parameter #7

41 (Frequency)

8

41009

Selection for Parameter #8

52 (Total Real Power)

9

41010

Selection for Parameter #9

56 (Total Reactive Power)

10

41011

Selection for Parameter #10

60 (Total Apparent Power)

11

41012

Selection for Parameter #11

48 (3 Phase True Power Factor)

12

41013

Selection for Parameter #12

70 (Real Energy Net (kWh))

13

41014

Selection for Parameter #13

62 (Status 1 Count x1)

14

41015

Selection for Parameter #14

64 (Status 2 Count x1)

15

41016

Selection for Parameter #15

79 (Real Power Demand)

16

41017

Selection for Parameter #16

8 (Status Input States)

Advertising
This manual is related to the following products: