Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 95

Advertising
background image

Rockwell Automation Publication 1408-UM001D-EN-P - September 2013

95

PowerMonitor 1000 Data Tables Appendix A

Table 35 - Unit Status Log Results Parameters

CSP File No.

N25

CIP Instance

18

Applies to

All models

No. of Elements

13

No. of Words

13

Data Type

Integer

Data Access

Read

Table 36 - Unit Status Log Results

Element

No.

Modbus

Address

Element Name

Range

Description

0

30601

Status Record Internal Identifier

1…50

Used to verify record sequence when returning multiple records.

1

30602

Timestamp Year of record

-

The year when the record was recorded.

2

30603

Timestamp Month/Day

-

The month and day when the record was recorded.

3

30604

Timestamp Hour/Minute

-

The hour and minute when the record was recorded.

4

30605

Timestamp Seconds/Hundredths

-

The seconds and hundredths when the record was recorded.

5

30606

Status Event Type

0…512

Indicates the type of status event that has occurred.

6

30607

General Code

0…4096

Indicates general information about the status event.

7

30608

Information Code

0…256

Indicates specific information about the status event.

8

30609

Reserved

0

Reserved for future use.

9

30610

Reserved

0

Reserved for future use.

10

30611

Reserved

0

Reserved for future use.

11

30612

Reserved

0

Reserved for future use.

12

30613

Reserved

0

Reserved for future use.