PowerMonitor 1000 Data Tables Appendix A

15

40131-32

Demand

Period Length

15 min

0…99

Specifies the desired period for demand

calculations. When set to 0 there are no

projected demand calculations. If the internal

timer is selected a setting of 0 turns the

demand function off.

16

40133-34

Number of

Demand

Periods

1

1…15

Specifies the number of demand periods to

average for demand measurement.

17

40135-36

Forced

Demand Sync

Delay

10 s

0…900 s

When the power monitor is configured for

external demand control the unit delays for xxx

seconds after the expected control pulse has

not been received. The demand period starts

over and a record is recorded in the status log.
0 = Wait forever

1…900 = Wait this many seconds before

starting a new demand period.
This setting becomes active when the demand

interval is set from -1…-99 minutes.

18

40137-38

Unit Error

Action

1

0…1

This parameter determines the action when a

unit error occurs.
0 = Halt on error and make status LED solid red

1 = Reset power monitor hardware.

19

40139-40

Software Error

Log Full Action

1

0…1

This parameter determines the action when a

firmware failure is detected and the error log is

full.
0 = Halt on error and wait for clear log

command, also make status LED solid red

1 = Perform a firmware reset.

20

40141-42

Reserved

0

0

Reserved for future use.

21

40143-44

Reserved

0

0

Reserved for future use.

Table 7 - Advanced Configuration

Element

No.

Modbus

Address

Range

Element

Name

Default

Value

Range

TR

1

TR

2

EM

1

EM

2

EM

3

Description