Rockwell Automation 1408-EMxx PowerMonitor 1000 Unit User Manual

Page 70

Advertising
background image

70

Rockwell Automation Publication 1408-UM001D-EN-P - September 2013

Appendix A PowerMonitor 1000 Data Tables

Table 4 - Analog Input Configuration Parameters

CSP File No.

F10

CIP Instance

3

Applies to

All models

No. of Elements

7

No. of Words

14

Data Type

Float

Data Access

Read/Write

Table 5 - Analog Input Configuration

Element

No.

Modbus

Address

Element Name

Default

Value

Range

Description

0

40001-2

Password

0

0…9999

When writing the complete table this parameter allows the input

data to be accepted. When writing a single parameter the separate

password table should be used. Returns -1 on a read.

1

40003-4

Voltage Mode

2

0…4

Should match the external electrical system and how it is wired to

the PowerMonitor’s voltage and current input terminals. Refer to

the installation manual wiring diagrams.
0 = Direct Delta

1 = Open Delta

2 = Wye

3 = Single Phase

4 = Demo

2

40005-6

PT Primary

480

1.00…

50,000

The first value of the PT ratio (xxx:xxx) indicating the nominal

voltage present at the high-end of the transformer. If no transformer

is used (for direct connect of up to 347V L-N or 600V L-L), set the PT

ratio to any valid 1:1 ratio (for example 480:480).

3

40007-8

PT Secondary

480

1.00…

600.00

The second value of the PT ratio (xxx:xxx) indicating the nominal

voltage present at the low-end of the transformer.

4

40009-10

CT Primary

5

5.00…

50,000

The first value of the CT ratio (xxx:5) indicating the nominal current

present at the high-end (primary side) of the transformer.
Example: PRI = 1000. Setting = 1000:5.
5 A is the nominal secondary current of the CT.

5

40011-12

System PF Setting

2

0…2

0 = Leading -97…89

1 = High -85…98

2 = Low -52…-95

6

40013-14

Reserved

0

0

Reserved for future use.