Troubleshooting for devicenet drives, Devicenet module status indicator o, Devicenet network status indicator – Rockwell Automation 2090 Ultra3000 Servo Drives Integration Manual User Manual

Page 109

Advertising
background image

Publication 2098-IN005C-EN-P — March 2008

Troubleshooting Your Ultra3000 Servo Drive

109

Troubleshooting for
DeviceNet Drives

These troubleshooting tables apply to Ultra3000-DN drives
(2098-DSD-xxx-DN, 2098-DSD-xxxX-DN, 2098-DSD-HVxxx-DN, or
2098-DSD-HVxxxX-DN).

DeviceNet Module Status Indicator

DeviceNet Network Status Indicator

Module Status
Indicator

Status

Potential Cause

Possible Resolution

Off

Not powered

No power

There is no power going to the device.

Steady-green

Operational

Normal operation

Normal operation - no action needed.

Flashing-green

Device is in
stand-by

Processing or waiting
for input

Normal operation - no action needed.

Flashing-red

Recoverable fault

Not operational

Power cycle or reset the drive.

Steady-red

Unrecoverable
fault

Drive problem

1. Check drive for power-up error.

2. Replace drive.

Flashing-red/
Flashing-green

Self testing

Self-test in progress

The device is in self test, wait.

Network Status
Indicator

Status

Potential Cause

Possible Resolution

Off

Not powered

Not online

No power going to
the device

Failed Duplicate
MAC ID check

1. Check the Module Status indicator to verify that the drive is powered.

2. Check that one or more nodes are communicating on the network.

3. Check that at least one other node on the network is operational and the data

rate is the same as the drive.

Flashing-green

Online

Not connected

Passed Duplicate
MAC ID check

No connection
established

No action is needed. The indicator is flashing to signify that there are no open
communication connections between the drive and any other device. Any connection
(I/O or explicit message) made to the drive over DeviceNet will cause the indicator to
stop flashing and remain Steady-ON for the duration of any open connection.

Steady-green

Online

Connected

One or more
connections
established

No action needed. This condition is normal.

Flashing-red

Online

Time-out

I/O connection timed
out

1. Re-initiate I/O messaging by the master controller.

2. Reduce traffic or errors on the network so that messages can get through within

the necessary time frame.

Steady-red

Network Failure

Failed Duplicate
MAC ID check

Bus-off

1. Ensure that all nodes have unique addresses.

2. If all node addresses are unique, examine network for correct media installation.

3. Ensure that all nodes have the same Data Rate.

Advertising