Commissioning Your Ultra3000 Drive

11. Using this table, determine the sequence of these three inputs that

correspond to the preset velocity entered.

12. Apply 12…24V dc to input 1.

Input 1 was configured as Drive Enable in a previous step.

a. Verify the toolbar Enable icon is active, indicating the drive is

enabled.

b. Verify the Drive Enabled lamp is ON (yellow)

c. If none of the Preset Selects are ON, observe the motor

running at the selected speed (rpm) for Preset 0 (10 rpm in
this example).

13. Double-click the Monitor branch.

The (default) Drive Status parameters display.

Preset Selects

Binary Code

Selected Preset or Index

5

4

3

2

1

0

Select up to 64 locations via preselect inputs

5…0 by using BCD format.

(codes for preset selects 1 and 0 are shown)

0

0

0

0

0

0

Preset 0 or Index 0 is selected.

0

0

0

0

0

1

Preset 1 or Index 1 is selected.

0

0

0

0

1

0

Preset 2 or Index 2 is selected.

0

0

0

0

1

1

Preset 3 or Index 3 is selected.

1

1

1

1

1

1

Preset 64 or Index 64 is selected.