Commissioning Your Ultra3000 Drive

Follow these steps to use digital outputs to indicate an event has
occurred.

1. Double-click the Digital Outputs branch.

2. Use the pull-down menu to change the output values.

3. Close the Digital Outputs dialog.

4. Apply 12…24V dc to input 1.

Input 1 was configured as Drive Enable in a previous step.

5. Apply 12…24V dc to input 3 (momentarily) to start the homing

routine.

6. Apply 12…24V dc to input 4 (momentarily) to simulate a homing

sensor.

The drive goes into reverse to find the marker and completes the
homing routine.

7. Double-click the Digital Outputs branch.

8. Observe Digital Outputs status.

Output 1 is on because the drive is enabled.

Output 2 is on because the drive has been homed.

Output 3 is on because the motor is in position.

9. Apply 12…24V dc to input 5 and observe Digital Outputs 2 and 3

change states.

10. Apply 12…24V dc to input 6 (momentarily) to stop the indexing

move.