Instance 101 - XM-123 Module Measurements

This is the default assembly that is sent within the I/O Poll Response message
when an I/O Poll request is received from a DeviceNet master.

Instance 102 - XM-123 Module Measurements

This is an alternate assembly for the I/O Poll Response message.

3

Relay 4
Status

0

Alarm 8 Status

Alarm 7 Status

4

Relay 5
Status

0

Alarm 10 Status

Alarm 9 Status

5

0

0

Alarm 12 Status

Alarm 11 Status

Table C.10 Instance 100 Data Format (Alarm and Relay Status Values Assembly)

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Table C.11 Instance 101 Data Format (XM-123 Measurement Values Assembly)

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0 - 3

Channel 1 Tracking Magnitude value

4 - 7

Channel 2 Tracking Magnitude value

8 - 11

Speed value

12 - 15

Channel 1 Overall value

16 - 19

Channel 2 Overall value

20 - 23

Channel 1 Tracking Phase value

24 - 27

Channel 2 Tracking Phase value

28 - 31

Channel 1 DC Bias value

32 - 35

Channel 2 DC Bias value

Table C.12 Instance 102 Data Format (XM-123 Measurement Values Assembly)

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0 - 3

Channel 1 Bandpass value

4 - 7

Channel 2 Bandpass value

8 - 11

Channel 1 Overall value

12 - 15

Channel 2 Overall value

16 - 19

Speed value

20 - 23

Channel 1 DC Bias value

24 - 27

Channel 2 DC Bias value

28 - 31

0

32 - 35

0