Publication GMSI10-UM003D-EN-P - May 2010

50

Channel Transducer
Parameters

The channel transducer parameters define the characteristics of the
transducers you will be using with the module. Use the parameters to
configure the transducer sensitivity, operating range, and power requirements.
There are two instances of the channel transducer parameters, one for each
channel.

TIP

The Channel LED will flash red when a transducer fault
condition exists on the channel even if you are not using
the channel. You can keep the Channel LED from flashing
red on unused channels by configuring the channel
transducer parameters as follows:

Set the unused channel’s Fault High and Fault Low to

greater than zero and less than zero, respectively. For
example, set Fault High to +18 volts and set Fault Low
to -18 volts.

Disable the unused channel’s transducer power by

clearing the Enable IEPE Power check box.

Channel Transducer Parameters

Parameter Name

Description

Values/Comments

Channel Name (XM Serial
Configuration Utility only)

A descriptive name to help identify the channel in
the XM Serial Configuration Utility.

Maximum 18 characters

Controls whether to provide standard accelerometer
(IEPE) power to the transducer.

Refer to Connecting the Transducer on page 27 for
wiring requirements.

Sensitivity

The sensitivity of the transducer in millivolts per
Eng. Unit.

The sensitivity value is included with
the transducer’s documentation or it
may be imprinted on the side of the
transducer.

XM Configuration
Utility

EDS File

Enable IEPE
Power

IEPE Power

XM Configuration
Utility

EDS File

Check = Enable

Enabled

Clear = Disable

Disabled