Channel signal processing parameters – Rockwell Automation 1440-VAD02-01RA XM-123 Aeroderivative Module User Manual

Page 60

Advertising
background image

Publication GMSI10-UM003D-EN-P - May 2010

52

Channel Signal Processing
Parameters

The channel signal processing parameters determine the signal processing that
will be performed on the input signals. Use these parameters to select the
output data units and the low cutoff frequency for each channel. There are two
instances of the signal processing parameters, one for each channel.

Full Scale

The maximum signal level expected to be processed
by the channel. This value is used to determine the
programmable gain settings across each stage of the
channel’s analog signal processing circuit.

Volt

Important: See Appendix D for further
guidance and recommended Full Scale
value settings.

Auto Full Scale (XM Serial
Configuration Utility only)

Calculates a new Full Scale value based upon the
current input signal level.

Enter a safety factor value greater
than or equal to 1.0.

The safety factor is a number that will
be multiplied to the current signal
level to determine the new Full Scale
setting.

Channel Transducer Parameters

Parameter Name

Description

Values/Comments

Channel Signal Processing Parameters

Parameter Name

Description

Values/Comments

Output Data Unit

The data units of the measured values.

The available options depend on the
Eng. Units selection. See page
51.

Very Low HPF Frequency (EDS
File only)

Shows the corner frequency for the Very Low high
pass filter option.

Eng. Units

Output Data
Unit Options

g

g

ips

mm/sec

ips or mm/sec

ips

mil

mm/sec

um

mils or um

mils

um

Volt

volt

Pa or psi

Pa

psi