Publication GMSI10-UM003D-EN-P - May 2010

85

Alarms

Number

Alarm Parameters

Operators

Hysteresis

Startup Inhibit/Setpoint Multiplication

Speed Inhibit

12 alarm and danger pairs

Speed, Overall, DC Bias, Band or Tracked
Magnitude from either channel

Greater than
Less than
Inside range
Outside range

User configurable in software

Period: 0 to 1092 minutes, adjustable in 0.1
minute increments
Inhibit/multiplication function: floating
point value in the range of 0 to 10

A speed range may be specified for each
alarm. When applied, the alarm is disabled
when speed is outside of the defined range.

Relays

Number

On-board Relay Rating

Failsafe

Latching

Time Delay

Single on-board relay, two sets of contacts -
DPDT (2 Form C)
Four additional relays when interconnected
to an XM-441 Expansion Relay module, or
Four virtual relays whose status can be
used by remote Control Systems or the
XM-440 Master Relay module

Maximum Voltage: 120V dc, 125V ac
Maximum Current: 3.5 A*
Minimum Current: 0
Maximum Power: 60 W, 62.5 VA

*Max current is up to 40°C, then derates to 2 A

at 65°C

Agency Rating:
120V ac @ 0.5 A
110V dc @ 0.3 A
30V dc @ 1.0 A

Normally energized (failsafe), or
Normally de-energized (non-fail-safe)

Latching, or
Non-latching

0 to 65.53 seconds, adjustable in 0.01
second increments

XM-123 Technical Specifications