Services

1

Attributes can only be set while the device is in Program Mode. See the description of the Device Mode Object
for more information.

Transducer Object
(Class ID 328

H

)

The Transducer Object models a transducer.

Class Attributes

The Transducer Object provides no class attributes.

Instances

There are 3 instances of this object. Transducer Object instance 1 is for
vibration channel 1. Transducer Object instance 2 is for vibration channel 2.
And Transducer Object instance 3 is for the tachometer channel.

Instance Attributes

Table C.47 Tachometer Channel Object Services

Service
Code

Class/Instance Usage

Name

Description

0E

h

Instance

Get_Attribute_Single

Returns a single attribute.

10

h

Instance

Set_Attribute_Single

Sets a single attribute.

1

Table C.48 Transducer Object Instance Attributes

Attr ID

Access
Rule

Name Data

Type

Description

Semantics

3

Get

DC Bias

REAL

The measured average DC
bias of the transducer
signal in volts.

Volts

4

Get

Status

BOOL

Indicates whether a
transducer fault exists
(the measured DC Bias is
outside the range
specified by Fault High
and Low).

0 = No fault
1 = A transducer fault exists