The device test occurs after the LED test. The Module Status (MS) indicator is
used to indicate the status of the device self-test.

Refer to Module Indicators on page 45 for more information about the LED
indicators.

Manually Resetting Relays

The XM-123 has an external reset switch located on top of the module, as
shown in Figure 2.34.

Figure 2.34 Reset Switch

The switch can be used to reset all latched relays in the module. This includes
the relays in the Expansion Relay Module when it is attached to the XM-123.

MS Indicator State

Description

Flashing Red and Green

Device self-test is in progress.

Solid Green or Flashing Green

Device self-test completed successfully,
and the firmware is valid and running.

Flashing Red

Device self-test completed, the hardware is
OK, but the firmware is invalid. Or, the
firmware download is in progress.

Solid Red

Unrecoverable fault, hardware failure, or
Boot Loader program may be corrupted.

IMPORTANT

The Reset switch resets the relays only if the input is no
longer in alarm or the condition that caused the alarm is no
longer present.

AERODERIVATIVE

1440-VAD02-01RA

Press the Reset
Switch to reset the
relays