Publication GMSI10-UM003D-EN-P - May 2010

122

Services

1

Attributes can only be set while the device is in Program Mode. See the description of the Device Mode Object
for more information.

Band Measurement Object
(Class ID 31E

H

)

The Band Measurement Object models the measurement of the amplitude of a
signal within a narrow frequency range.

Class Attributes

The Band Measurement Object provides no class attributes.

17

Get/Set

Speed Range
Low

REAL

Indicates the lesser
threshold of the machine
speed range for which the
alarm is enabled (disabled
at lesser speeds).

CPM
(Must be less than Speed
Range High
)

18

Get/Set

Name

STRING2

A name to help identify
this alarm.

19

Get/Set

Measurement
Identifier

EPATH

Identifies the
measurement object to
which this alarm is
applied.

See Parameter Object instances
7 to 18.

20

Get/Set

Inhibit Tach
Fault

BOOL

Determines whether the
Tach Fault status is
prohibited during the
startup period.

0 = Tach Fault allowed
1 = Tach Fault inhibited

Table C.28 Alarm Object Instance Attributes

Attr ID

Access
Rule

Name Data

Type

Description

Semantics

Table C.29 Alarm Object Services

Service
Code

Class/Instance Usage

Name

Description

0E

h

Instance

Get_Attribute_Single

Returns a single attribute.

10

h

Instance

Set_Attribute_Single

Sets a single attribute.