Figure 2.23 Powered Sensor to Channel 1 Wiring

ATTENTION

Figures 2.23 and 2.24 show the wiring of a Model 580
Vibration Pickup, which is a +24V transducer. The +24V
sensors powered from pin 25 do not utilize the redundant
power connection to the XM-123. So if primary 24V power
is lost, the +24V sensor will lose power regardless of
whether the XM-123 remains powered through the
redundant power terminals.

If redundant power is required then use a redundant power
supply (Allen-Bradley 1606-series is recommended).

0

16

37

+24V DC

Common

Signal

5

6

Channel 1 Input Signal

Signal Common

Shield

+24V DC

TYPICAL WIRING FOR MODEL 580 VIBRATION PICKUP

TO XM-123 AERODERIVATIVE MODULE CHANNEL 1

Cable shield not
connected at this end

25

Jumpering terminal 5
to terminal 6 configures
CH 1 buffer for -5V to +24V

Advertising