Figure 2.23 powered sensor to channel 1 wiring – Rockwell Automation 1440-VAD02-01RA XM-123 Aeroderivative Module User Manual
Page 41
Publication GMSI10-UM003D-EN-P - May 2010
33
Figure 2.23 Powered Sensor to Channel 1 Wiring
ATTENTION
Figures 2.23 and 2.24 show the wiring of a Model 580
Vibration Pickup, which is a +24V transducer. The +24V
sensors powered from pin 25 do not utilize the redundant
power connection to the XM-123. So if primary 24V power
is lost, the +24V sensor will lose power regardless of
whether the XM-123 remains powered through the
redundant power terminals.
If redundant power is required then use a redundant power
supply (Allen-Bradley 1606-series is recommended).
0
16
37
+24V DC
Common
Signal
5
6
Channel 1 Input Signal
Signal Common
Shield
+24V DC
TYPICAL WIRING FOR MODEL 580 VIBRATION PICKUP
TO XM-123 AERODERIVATIVE MODULE CHANNEL 1
Cable shield not
connected at this end
25
Jumpering terminal 5
to terminal 6 configures
CH 1 buffer for -5V to +24V