XM-123 Full Scale Tables

Use the following tables to help you determine the optimal Full Scale value for
the XM-123 module. Refer to the table that corresponds to the units of
vibration that will be used for monitoring.

Table D.1 XM-123 Measuring Acceleration with Accelerometer (100 mV/g)

Max Vibration Level

Full Scale Setting

g’s peak

1Hz HPF

5Hz HPF

10Hz HPF

40Hz HPF

1000Hz HPF

1

0.1

5

0.75

10

1

30

3

40

4

50

5

Table D.2 XM-123 Measuring Velocity with Accelerometer (100 mV/g)

Max Vibration Level

Full Scale Setting

Max High Frequency Peak Amplitude

ips peak mm/s RMS

1Hz HPF

5Hz HPF

10Hz HPF

40Hz HPF

1000Hz HPF

(g pk)

0.3

10

N/A

0.005

0.01

0.03

0.75

4

1

40

N/A

4

3

100

0.009

0.018

0.072

4

10

360

0.085

0.17

0.67

12

30

1000

0.25

0.5

2.2

40

100

3600

0.83

1.66

6.66

120

Table D.3 XM-123 Measuring Velocity with Velocimeter (100 mV/ips)

Max Vibration Level

Full Scale Setting

ips peak

mm/s RMS

1Hz HPF

5Hz HPF

10Hz HPF

40Hz HPF

1000Hz HPF

3

100

0.75

10

360

1

20

700

2

30

1000

3

Table D.4 XM-123 Measuring Displacement with Velocimeter (100 mV/ips)

Max Vibration Level

Full Scale Setting

mils pp

micrometers pp

1Hz HPF

5Hz HPF

10Hz HPF

40Hz HPF

1000Hz HPF

5

125

N/A

0.05

0.1

0.35

N/A

10

250

0.1

0.2

0.7

50

1250

0.15

0.3

1.05