Services, Alarm object (class id 31dh), Class attributes – Rockwell Automation 1440-VAD02-01RA XM-123 Aeroderivative Module User Manual

Page 128: Instances, Instance attributes, Class attributes instances instance attributes, Alarm object (class id 31d, Class attributes instances

Advertising
background image

Publication GMSI10-UM003D-EN-P - May 2010

120

Services

Alarm Object
(Class ID 31D

H

)

The Alarm Object models a two-stage (alert and danger levels) alarm.

Class Attributes

Instances

There are 12 instances of this object

Instance Attributes

Table C.26 Acknowledge Handler Object Services

Service
Code

Class/Instance Usage

Name

0E

h

Instance

Get_Attribute_Single

10

h

Instance

Set_Attribute_Single

Table C.27 Alarm Object Class Attributes

Attr ID

Access
Rule

Name Data

Type

Description

Semantics

1

Get

Revision

USINT

Revision of the
implemented object.

2 (indicates that Threshold
Multiplier
is a REAL instead of
USINT)

Table C.28 Alarm Object Instance Attributes

Attr ID

Access
Rule

Name Data

Type

Description

Semantics

3

Get

Alarm Status

3 BITS

The current status of the
alarm.

0 = Normal
1 = Alert (alarm)
2 = Danger (shutdown)
3 = Disarm
4 = Xdcr Fault
5 = Module Fault
6 = Tachometer Fault

4

Get/Set

Alarm Enable

BOOL

Indicates whether this
alarm object is enabled.

0 = Disabled
1 = Enabled

Advertising