Rockwell Automation 1440-VAD02-01RA XM-123 Aeroderivative Module User Manual

Page 73

Advertising
background image

Publication GMSI10-UM003D-EN-P - May 2010

65

Enable

Enable/disable the selected relay.

Note: The Relay Current Status is set to "Not
Activated" when the relay is disabled. See page 78.

Controls whether the relay must be explicitly reset
after the alarm subsides.

Activation Delay

Enter the length of time for which the Activation
Logic
must be true before the relay is activated. This
reduces nuisance alarms caused by external noise
and/or transient vibration events.

Important: True Peak and True Peak-to-Peak signal
detection is more sensitive to transients and noise.
To avoid false relay trips, it is strongly recommended
that the Activation Delay value is greater than the
Overall Time Constant value when Signal
Detection
is set to "True Peak" or "True
Peak-to-Peak." Refer to Overall Measurement
Parameters on page 53.

Enter a value from 0.00 to 65.53
seconds, adjustable in increments of
0.01 seconds.

Default is 1 second

Sets the relay activation logic.

A or B - Relay is activated when either Alarm A or
Alarm B meets or exceeds the selected Alarm
Status
condition(s).

A and B - Relay is activated when both Alarm A
and Alarm B meet or exceed the selected Alarm
Status
condition(s).

A Only - Relay is activated when Alarm A meets
or exceeds the selected Alarm Status
condition(s).

Options: A only

A or B
A and B

Sets the alarm(s) that the relay will monitor. The
alarm must be from the same device as the relay.
When the Activation Logic is set to "A and B" or "A
or B," you can select an alarm in both Alarm A and
Alarm B. The system monitors both alarms. When
the Activation Logic is set to "A Only," you can
select an alarm only in Alarm A.

Alarm No. 1 to 12

Note: You can only select an alarm
that is enabled.

Relay Parameters

Parameter Name

Description

Options/Comments

XM Configuration
Utility

EDS File

Check to Enable

Enabled

Clear to Disable

Disabled

XM Configuration
Utility

EDS File

Latching

Latching
Option

XM Configuration
Utility

EDS File

Check means
latching (relay must
be explicitly reset)

Latching

Clear means
non-latching (relay
is reset once the
alarm condition has
passed)

Nonlatching

XM Configuration
Utility

EDS File

Activation Logic

Logic

XM Configuration
Utility

EDS File

Alarm A/B

Alarm
Identifier
A/B