Rockwell Automation 1440-VAD02-01RA XM-123 Aeroderivative Module User Manual

Page 94

Advertising
background image

Publication GMSI10-UM003D-EN-P - May 2010

86

Voting Logic

Reset

Activation On

Single or paired “And” or “Or” logic applied
to any alarm

Local reset switch on top of module
Remote reset switch wired to terminal base
Digital reset command via serial or
DeviceNet interface

Alarm Status:

Normal
Alert
Danger
Disarm
Transducer fault
Module fault
Tacho fault

Peak Speed Capture

The XM-123 retains the value of the highest
speed observed since module power was
cycled or the “peak speed” value was
manually reset.

Non-Volatile Configuration

A copy of the module configuration is
retained in non-volatile memory from where
it is loaded upon power up*.

*The configuration stored in non-volatile

memory can be deleted only by a command
sent via the serial interface, using the Serial
Configuration Utility, or via DeviceNet from any
compliant software application.

Accuracy (minimum)

±1% of full scale range for the channel
±1% of alarm setpoint for speed

Power

Module

Consumption

Heat Production

Transducer

+21.6 to +26.4V dc

Maximum: 300 mA
Typical: 175 mA

Maximum: 7 Watts (24 BTU/hr)
Typical: 4 Watts (14 BTU/hr)

Isolated 24V dc, user configurable with
wiring

Environmental

Operating Temperature

Storage Temperature

Relative Humidity

Conformal Coating

-20 to +65°C (-4 to +149°F)

-40 to +85°C (-40 to +185°F)

95% non-condensing

All printed circuit boards are conformally
coated in accordance with IPC-A-610C.

XM-123 Technical Specifications

Product Feature

Specification

Advertising