Data Parameters

The Data parameters are used to view the measured values of the input
channels, as well as to monitor the status of the channels, alarms, and relays.

Monitor Data Parameters

TIP

To view all the data parameters in the XM Serial
Configuration Utility, click the View Data tab.

Monitor Data Parameters

Parameter Name

Description

Values/Comments

States whether a transducer fault exists on the
associated channel. If a fault exists, the overall,
band, magnitude, phase and dc bias values may not
be accurate.

Possible status values: No Fault

Fault

Shows the measured overall band value.

The XM-123 can produce the
bandpass measurement only when the
Bandpass Filter is selected. See
Aeroderivative Measurement
Parameter on page 55.

Tracked Magnitude Value

Shows the measured magnitude value at the tracked
multiple of the machine speed.

Tracking Measurement Requirements:

The Tracking Filter must be
selected. See Aeroderivative
Measurement Parameter on
page 55.

The tachometer must be enabled
(Pulses Per Revolution set to 1 or
more).

Tracked Phase Value

Shows the measured phase value at the tracked
multiple of the machine speed.

Overall

Shows the measured overall value.

Shows the measured average DC offset of the
transducer signal. This value is compared with Fault
High
and Fault Low to determine whether the
transducer is working properly.

XM Configuration
Utility

EDS File

Transducer Fault

Transducer
Status

XM Configuration
Utility

EDS File

Bandpass

Band
Measured
Value

XM Configuration
Utility

EDS File

Xdcr DC Bias

Measured
DC Bias