Basic operations, Powering up the module – Rockwell Automation 1440-VAD02-01RA XM-123 Aeroderivative Module User Manual

Page 55

Advertising
background image

Publication GMSI10-UM003D-EN-P - May 2010

47

1

Normal condition when the module is not a slave to an XM-440, PLC, or other master device.

Channel 1, Channel 2, and Tachometer Status Indicators

Setpoint Multiplier Indicator

Relay Indicator

Basic Operations

Powering Up the Module

The XM-123 performs a self-test at power-up. The self-test includes an LED
test and a device test. During the LED test, the indicators will be turned on
independently and in sequence for approximately 0.25 seconds.

Red

Flashing

One or more I/O connections are in the timed-out state.

Solid

Failed communications (duplicate MAC ID or Bus-off).

Color

State

Description

No color

Off

Normal operation within alarm limits on the channel.

No power applied to the module, look at Module
Status LED.

Yellow

Solid

An alert level alarm condition exists on the channel
(and no transducer fault, tachometer fault, or danger
level alarm condition exists).

Flashing
(Tach LED only)

Tachometer fault (no transducer fault) condition exists
on the channel.

Red

Solid

A danger level alarm condition exists on the channel
(and no transducer fault or tachometer fault condition
exists).

Flashing

A transducer fault condition exists on the channel.

Color

State

Description

Yellow

Off

Setpoint multiplier is not in effect.

Solid

Setpoint multiplier is in effect.

Color

State

Description

Red

Off

On-board relay is not activated.

Solid

On-board relay is activated.

Color

State

Description