Rockwell Automation 1440-VAD02-01RA XM-123 Aeroderivative Module User Manual

Page 80

Advertising
background image

Publication GMSI10-UM003D-EN-P - May 2010

72

The XM module collects a coast-down trend when the machine speed falls
through the Maximum Speed - 8 RPM, and stops when the machine speed
crosses either the Minimum Speed or the Maximum Speed. The module
collects data when the machine speed is decreasing or increasing during a
coast-down trend (for example, a coast-down restart).

The XM-123 can only store one startup/coast-down trend. Unless the
startup/coast-down trend is latched, the trend data is overwritten with new
data when the next trigger occurs.

The SU/CD trend parameters define the trend data that is collected by the
module during the startup or coast-down of a machine. Use these parameters
to configure the measurements included in the startup and coast-down trend
records, the interval between trend records, and the minimum and maximum
speed limits at which record collection starts and stops.

IMPORTANT

The SU/CD Trend parameters are not included in the EDS
file and cannot be edited using generic configuration tools
such as RSNetWorx for DeviceNet.

SU/CD Trend Parameters

Parameter Name

Description

Values/Comments

Enable SU/CD Trend

Enable/disable the SU/CD trend measurements.
Select to configure the SU/CD trend measurements.

Check to enable.
Clear to disable.

Select Measurements

Sets the measurements to be collected and stored in
the module.

Note: The Speed measurement is always included in
the startup/coast-down trend.

More than one measurement can be
selected.

Important: Make certain to check
your filter selection (Tracking Filter
or Bandpass Filter).

The XM-123 can produce either the
bandpass or tracking measurements
depending on which filter was
selected. If you select a band or
tracking measurement that is not
being produced by the module, a trend
of zeroes will be stored for that
measurement.

For example, if you select the "CH1
Band" measurement but the
Bandpass Filter for Channel 1 is not
selected, the module will store zeroes
in the trend for the CH1 Band
measurement.

Number of Records

The maximum number of measurement sets that can
be collected in the trend buffer. The measurement
sets make up the trend data.

The Number of Records is
automatically calculated based upon
the number of Trended
Measurements
selected.