Instances, Instance attributes, Instances instance attributes – Rockwell Automation 1440-VAD02-01RA XM-123 Aeroderivative Module User Manual

Page 131

Advertising
background image

Publication GMSI10-UM003D-EN-P - May 2010

123

Instances

There are 2 instances of this object.

Instance Attributes

Table C.30 Band Measurement Object Instances

Instance

Description

1

Channel 1 Band Measurement

2

Channel 2 Band Measurement

Table C.31 Band Measurement Object Instance Attributes

Attr ID

Access
Rule

Name Data

Type

Description

Semantics

3

Get

Band Value

REAL

The measured band value. See Data Units

4

Get

Status

BOOL

Indicates if a fault or
alarm has occurred.

0 = Operating without alarms or
faults
1 = Alarm or fault condition
exists, the Band Value
attribute may not represent the
actual field value.

5

Get

Data Units

ENGUNIT

The units context of the
Band Value attribute.

This attribute is read only. It is
set according to the Output
Data Units
attribute of the
associated Channel Object
instance. See page 125.

7

Get/Set

Minimum
Frequency

REAL

The minimum frequency
that is included in the
band measurement.

25 to 1000 Hz

8

Get/Set

Maximum
Frequency

REAL

The maximum frequency
that is included in the
band measurement.

100 to 5500 Hz

The Maximum Frequency must
be greater than or equal to
Minimum Frequency.