Publication GMSI10-UM003D-EN-P - May 2010

131

Services

1

Attributes can only be set while the device is in Program Mode. See the description of the Device Mode Object
for more information.

8

Get/Set

Damping Factor

REAL

The damping factor
associated with output
smoothing filter for the
RMS and DC meters (not
used with peak meters).

0.7072 to 1.0

The Damping Factor is used in
conjunction with the Time
Constant
to vary the
characteristics of the response
of the filter used in calculating
the Overall Value. An Overall
Value
for a measurement with
Damping Factor near 1.0 will
slowly rise or fall for the full
settling time specified by the
Time Constant before reaching
the final value. An Overall
Value
for a measurement with
a Damping Factor near 0.7072
will rise or fall quickly and may
overshoot the final value before
reaching the final value for a
given input signal.
The Damping Factor is only used
in conjunction with RMS
measurement types.

9

Get/Set

Overall Filter

USINT

Overall filter type applied
to the input signal before
the measurement is
performed.

0 = None
1 = Low Pass Filter
2-255 Reserved

10

Get/Set

Low Pass
Corner
Frequency

UINT

The corner frequency of
the low pass filter.

200 to 20000 Hz

The Low Pass Corner Frequency
only has meaning while Overall
Filter
is set to Low Pass Filter.

Table C.39 Overall Measurement Object Instance Attributes

Attr ID

Access
Rule

Name Data

Type

Description

Semantics

Table C.40 Overall Measurement Object Services

Service
Code

Class/Instance Usage

Name

Description

0E

h

Instance

Get_Attribute_Single

Returns a single attribute.

10

h

Instance

Set_Attribute_Single

Sets a single attribute.