30

Figure 2.19 Non-Contact Sensor to Channel 1 Wiring

Figure 2.20 Non-Contact Sensor to Channel 2 Wiring

TYPICAL WIRING FOR NON-CONTACT SENSOR

TO XM-123 AERODERIVATIVE MODULE CHANNEL 1

COM

SIG

-24

Channel 1 Input Signal

-24V DC

0

16

Signal Common

21

5

Jumpering terminal 5 to
terminal 21 configures
CH 1 buffer for -24V to +9V

Isolated Sensor Driver

Shield

Shield
Floating

37

TYPICAL WIRING FOR NON-CONTACT SENSOR

TO XM-123 AERODERIVATIVE MODULE CHANNEL 2

COM

SIG

-24

Channel 2 Input Signal

-24V DC

1

17

22

Signal Common

21

Jumper ing terminal 21 to
terminal 22 configures
CH 2 buffer for -24V to +9V

Isolated Sensor Driver

Shield

Shield
Floating