Rockwell Automation 1440-VAD02-01RA XM-123 Aeroderivative Module User Manual
Page 38
Advertising
Publication GMSI10-UM003D-EN-P - May 2010
30
Figure 2.19 Non-Contact Sensor to Channel 1 Wiring
Figure 2.20 Non-Contact Sensor to Channel 2 Wiring
TYPICAL WIRING FOR NON-CONTACT SENSOR
TO XM-123 AERODERIVATIVE MODULE CHANNEL 1
COM
SIG
-24
Channel 1 Input Signal
-24V DC
0
16
Signal Common
21
5
Jumpering terminal 5 to
terminal 21 configures
CH 1 buffer for -24V to +9V
Isolated Sensor Driver
Shield
Shield
Floating
37
TYPICAL WIRING FOR NON-CONTACT SENSOR
TO XM-123 AERODERIVATIVE MODULE CHANNEL 2
COM
SIG
-24
Channel 2 Input Signal
-24V DC
1
17
22
Signal Common
21
Jumper ing terminal 21 to
terminal 22 configures
CH 2 buffer for -24V to +9V
Isolated Sensor Driver
Shield
Shield
Floating
38