Rockwell Automation 1440-VAD02-01RA XM-123 Aeroderivative Module User Manual

Page 141

Advertising
background image

Publication GMSI10-UM003D-EN-P - May 2010

133

6

Get/Set

Failsafe Enable

BOOL

Indicates whether this
relay is normally
energized (activated
during power loss).

0 = Non-failsafe (not normally
energized)
1 = Failsafe (normally energized)

7

Get/Set

Delay

UINT

The time period that the
voting logic must be true
before the relay is
activated.

0.00 to 65.53 seconds
(specified in milliseconds)

8

Get/Set

Name

STRING2

A name to help identify
the relay.

18 characters maximum

9

Get/Set

Alarm Level

BYTE

Specifies what alarm
status values will cause
the relay to activate.

0 = Normal
1 = Alert
2 = Danger
3 = Disarm
4 = Xdcr Fault
5 = Module Fault
6 = Tachometer Fault

10

Get/Set

Alarm Identifier
A

EPATH

Identifies the first alarm
status the relay monitors.

11

Get/Set

Alarm Identifier
B

EPATH

Identifies the second
alarm status the relay
monitors.

12

Get/Set

Logic

USINT

Indicates the number of
associated alarms that
must have a status value
specified by Alarm Level
in order to activate the
relay.

0 = Ignore Alarm Identifier B
and activate the relay based on
the status of Alarm Identifier
A
.
1 = Activate the relay if the
status of either Alarm
Identifier A
or B matches any
of the statuses specified by
Alarm Level.
2 = Activate the relay if the
status of both Alarm Identifier
A
and B match any of the
statuses specified by Alarm
Level
.

14

Get

Relay Installed

BOOL

Indicates whether an
actual relay is associated
with this instance.

0 = Not installed
1 = Installed

Table C.42 Relay Object Instance Attributes

Attr ID

Access
Rule

Name Data

Type

Description

Semantics