Page 5-47

Chapter 5 Programming

5.11.4 Printer Out

This option allows the user to configure the Parallel Printer Port to print point data and/or events at a specific
interval. Under Program, System, use the UP (

↑) or DOWN (↓) Arrow Keys to highlight “Printer out” and press

ENTER. The Printer Out Menu will be displayed with the following options:

5.11.4.1 Data

This option allows the user to enable or disable the printing of Point Data to the printer. Use the UP (

↑) or

DOWN (

↓) Arrow Keys to highlight this menu choice and press ENTER. A window will pop up and show

the current status: “print data=NO*” if the unit will not print data, or “print data=YES*” if the unit is to print
data. Enable data to be printed by pressing YES or prevent data from being printed by pressing NO and
then press ENTER to return to the Printer Out Menu.

5.11.4.2 Events

This option allows the user to enable or disable the printing of Events to the printer. Use the UP (

↑) or

DOWN (

↓) Arrow Keys to highlight this menu choice and press ENTER. A window will pop up and show the

current status “print events=NO*” if the unit will not print events, or “print events=YES*” if the unit is to print
events. Enable events to be printed by pressing YES or prevent events from being printed by pressing NO
and then press ENTER. If you select YES, a window will be presented displaying “point X=YES*” or “point
X=NO*”. Use the UP (

↑) or DOWN (↓) Arrow Keys to select the point you wish to turn on or off, then press

NO to turn it off, or YES to turn it on. Press the ENTER button to activate your choice and automatically
select the next point. Press EXIT to return to the Printer Out menu.

NOTE: If Data and/or Events are set to “YES” and there is a problem with the printer (i.e. turned off, off line,

etc.), the error message “Printer Problem” will appear. Set Data and/or Events to “NO” to prevent this
error message from displaying until the problem has been fixed.

5.11.4.3 Data Interval

This option allows the user to set the time interval (in minutes) at which data or events are sent to the
printer. Use the UP (

↑) or DOWN (↓) Arrow Keys to highlight this menu choice and press ENTER. A

window will pop up and show “minutes

→XXXX←”. Use the keypad to enter the time interval and press

ENTER. A maximum of 1440 minutes (24 hours) may be entered. Setting the Data Interval to 0 will have
the unit send data every 15 seconds. Events print out as they occur.

5.11.4.4 Characters/Line

This option allows the user to set the number of characters per line (40 to 80). Use the UP (

↑) or DOWN

(

↓) Arrow Keys to highlight this menu choice and press ENTER. A window will pop up and show “characters/

line

→XX←”. Use the keypad to enter the number of characters per line and press ENTER.

NOTE: When printing, the Unit Tag and data groupings will not split. Both will wrap around to the next line

together.

5.11.4.5 Data Lines

This option allows the user to set the number of data lines printed between headers (0 to 255). Use the UP
(

↑) or DOWN (↓) Arrow Keys to highlight this menu choice and press ENTER. A window will pop up and

show “data lines

→XXX←”. Use the keypad to enter the number of data lines to be printed per page and

press ENTER. Setting the Data Line value to 0 will have the unit print the header every time data or events
are sent to the printer.