Appendix B – Configuring a 4-20 mA input to equal 0 to 150 gpm

Page 6 of 7

You will be prompted with

lo

→ ←

. Enter the low value of

your scale. For this example (0 to 150 gpm) select

0

and

touch

ENTER

.

NOTE:

You do not necessarily have to use the same scale

values that you selected in the point setup (0 to 150) you

could display/record a smaller portion of your full span,

90 to 150,for instance.

26.

You will now be prompted with

mid

→ ←

. Here you can

select the value that will be displayed at 50% of your span.

For this example select

75

(which is 50% of our full span,

150) and touch

ENTER

.

NOTE:

You do not necessarily have to enter the exact half

way point of your span. You could enter 30 for instance,

where 30 would be exactly half way between 0 and 150.

This would give you a high resolution side (0 to 30 gpm) and

a lower resolution side (30 to 150 gpm).

27

.

Finally, you will be prompted with

hi

→ ←

. Here you enter

the high end of your span. For this example select

150

and

touch

ENTER

. Then touch

EXIT

several times until you are

completely out of all menus.

28

.

The 0-150 scale complete with EFFLUENT and GPM should

be displayed on the Recorder. Use the VIEW button to

select a particular display to verify your work. You will also

notice that your high alarm set point is marked at 120 with

an arrow.

29

.

Use the up/down arrow keys to select

Scale ends

and touch

ENTER

. You will now be prompted with

places?

. Here you

can select the number of decimal places that will be

displayed on the virtual chart display. For this example use

the up/down arrow keys to select

0

and touch

ENTER

.

25.