Page 5-27

Chapter 5 Programming

5.6.12 Calculated Point Types

The following menu items are available through the Calculated Point Type menu:

Equation
High Peak
Low Peak
High/Low Difference
Moving Average
Time Average
Gated Timer
Totalize

Calculations may be performed on current point values of a single point or a group of points if set in Equations.
The calculations are performed after each scan of all measured points and the results are stored until the next
point scan.

NOTE: Moving Average can be set on channels A, B, C, D E, and F.

5.6.12.1 Equation

This Point Range of Calculated Point Types allows the user to program an equation to calculate a value of
one or more points and/or constants.

Operators Used for Equations - Forty operators are allowed in any one formula programmed. If the
equation does not compute, the display will read “bad operand”. The following operators are used:

P1 to PF

are used to represent Points

K1 to KF

are used to represent Constants

)

is a RIGHT Parenthesis

+

is Add

-

is Subtract

*

is Multiply

/

is Divide

^

is Fractional

**

is Raise to the Power (X

y

)

Sq

is Square Root

Ln

is Natural Logarithm

Lg

is Base Ten Logarithm

Ex

is Exponentiation (e

x

)

(

is a LEFT Parenthesis

The Point Setup menu for Equation will be displayed and may require programming the following parameters:

Point Tag

Section 5.6.5.1

Decimal fix

Section 5.6.5.4

Set Equation

Section 5.6.5.18

Engineering Units

Section 5.6.5.9

Alarm Setpoint

Section 5.6.5.10

Chart Scale

Section 5.6.5.11