Appendix D – Configuring the Totalizer

Page 1 of 5

Before setting up a math channel for totalization, you must

first have a “base” channel configured from which the

totalizer gets its information (i.e. a channel receiving a

signal from a flow meter that is proportional to flow rate).
For this example we will configure math channel A to be the

totalizer. Channel 1 is already configured as the flow rate

channel receiving a 4-20 mA signal from an open channel

flow meter (see Appendix B for setting up a 4-20 mA input).

The flow rate is 0 to 50 MGD (million gallons/day).

The numbers

1-9

and letters

A-F

will be displayed.

Channel A-F must be used for totalization channels

as

these channels will hold the total value in the event of a

power outage. (Channels 1-9 will not; they will reset.) For

this example select

A

and touch

ENTER

.

Prog point

and

Constants

will appear. Using the up/down

arrow keys select

Prog point

and touch

ENTER

.

Once in the main program menu use the up/down arrow

keys to select

Points

, then touch

ENTER

.

1.

4.

3.

2.

To Recorder

Appendix D

Configuring the Totalizer