Appendix B – Configuring a 4-20 mA input to equal 0 to 150 gpm

Page 3 of 7

A numerickeypad will now be displayed prompting you with

lo

→ ←

.

This is where you enter the low end of your range

or the equivalent value for 4 mA. For this example

(0 to 150 gpm) select

0

and touch

ENTER

.

You will now be prompted with

hi

→ ←

.

This is where you

enter the high end of your range of the equivalent value for

20 mA. For this example select

150

and touch

ENTER

.

You will now be back at the menu beginning with

Point tag

.

Using the up/down arrow keys select

Alarms

and touch

ENTER

.

Using the up/down arrow keys select

Eng units

and touch

ENTER

. An alpha-numerickeypad will appear prompting

you

units

→ ←

. You can enter up to 5 characters. Using

the

PAGE

,

PAGBK and SHIFT keys, if needed, enter the

desired engineering units. For this application enter GPM

and touch ENTER.

11.

12.

13.

14.

A menu prompting you

places?

will appear. Use the up/

down arrow keys to select the number of decimal places you

wish to be displayed and recorded. For this example select

0

and touch

ENTER.