Appendix B – Configuring a 4-20 mA input to equal 0 to 150 gpm

Page 4 of 7

You will be prompted with

alarm #?

. Each point has 5

internal alarm set points. You can use the up/down arrow

keys to scroll through 1, 2, 3, 4, or 5. Since this is the first

alarm set point for channel one, select

1

and touch

ENTER

.

The alarm types menu will now be displayed. Using the up/

down arrow keys you can select the type of alarm you wish

to configure. For this example we want to know when the

flow exceeds 120 gpm. Select

Type=high

and touch

ENTER

.

You will next be prompted

contact #?

. If your recorder is

fitted with alarm contact outputs, you can select which

contact will change state when the internal high alarm

activates. Using the up/down arrows you can select 0, 1, 2,

3, 4, 5 or 6. For this example select

2

and touch

ENTER.

Note:

If you do not have relays or do not wish to activate a

relay, select

0

(0 is the default setting) and touch

ENTER

.

A numeric keypad will now be displayed prompting you with

high

→ ←

. Enter

120

and touch

ENTER

.

16.

17.

18.

19.

Using the up/down arrow keys select

Alm limits

and touch

ENTER

.

15.