Page 5-26

Chapter 5 Programming

Programming Parameters - Selecting Log Linear point types requires setting up parameters like regular
Programming linear point types except that the Low and High Exponents must be set in Output Scales. From
the Point Type menu use the UP (

↑) or DOWN (↓) Arrow Keys to highlight “Log Linear” and press ENTER. The

Point Setup menu for Log Linear will be displayed and may require programming the following parameters:

Point Tag

Section 5.6.5.1

Input Scale

Section 5.6.5.2

Output Scale

Section 5.6.5.3 (Lo and Hi Exponents)

Exc. Currents

Section 5.6.5.5

Filter

Section 5.6.5.6

Engineering Units

Section 5.6.5.9

Alarm Setpoints

Section 5.6.5.10

Chart Scale

Section 5.6.5.11

Output Scale - All Log linear current and voltage inputs must be assigned low and high output scale
endpoints. The endpoints are the exponent values (the x in 10

x

) between +25 to -25.

5.6.10 Thermocouple (T/C) Point Types

Several Thermocouple type points are available for use. From the Point Type menu use the UP (

↑) or DOWN

(

↓) Arrow Keys to highlight “T/C” and press ENTER. A list of available thermocouple types is presented. Use

the UP (

↑) or DOWN (↓) Arrow Keys to highlight the desired thermocouple type:

J, K, T, E, R, S, B, C, Ninimo, or Nicro

and press ENTER. The Point Setup menu for Thermocouples will be displayed and may require programming the
following parameters:

Point Tag

Section 5.6.5.1

Decimal fix

Section 5.6.5.4

Filter

Section 5.6.5.6

Compensation

Section 5.6.5.7

Span/Offset

Section 5.6.5.8

Engineering Units

Section 5.6.5.9

Alarm Setpoints

Section 5.6.5.10

Chart Scale

Section 5.6.5.11

5.6.11 Resistance Temperature Detector (RTD)

Several types of RTD’s are available for selection. From the Point Type menu use the UP (

↑) or DOWN (↓)

Arrow Keys to highlight “Rtd” and press ENTER. A list of available RTD types is presented. Use the UP (

↑) or

DOWN (

↓) Arrow Keys to highlight the desired RTD type:

10

Ω Cu, 100Ω PT 385, 100Ω PT 392, 200Ω PT 385, 200Ω PT 392, 120Ω ni, 100Ω ni or 1000Ω ni

and press ENTER. The Point Setup menu for Rtd’s will be displayed and may require programming the
following parameters:

Point Tag

Section 5.6.5.1

Decimal fix

Section 5.6.5.4

Filter

Section 5.6.5.6

Span/Offset

Section 5.6.5.8

Engineering Units

Section 5.6.5.9

Alarm Setpoint

Section 5.6.5.10

Chart Scale

Section 5.6.5.11