Monarch Instrument DC 2000 User Manual

Page 151

Advertising
background image

Appendix D– Configuring the Totalizer

Page 3 of 5

You will now be back at the menu starting with

Point tag

.

Use the up/down arrow keys to select

Basepoint

and touch

ENTER

. You will be prompted with

base pt?

. Use the up/

down arrow keys to select the channel from which the

totalizer will derive its information. For this example, select

channel

1

and touch

ENTER.

You should now be back at the

Point tag

menu. Use the

up/down arrow keys to select

Flowrate

and touch

ENTER

.

You will again be back at the

Point tag

menu. Use the

up/down arrow keys to select

Eng units

and touch

ENTER.

11.

12.

13.

14.

The menu displaying the various flow rates should appear.

Use the up/down arrow keys to select the rate that matches

that of your flow meter. In this example our flow meter on

channel one measures millions of gallons per day, so select

flow= /day

and touch

ENTER

. You will have to touch

EXIT

to leave this menu.

You will be prompted with

places>?

(0, 1, 2, 3, 4 or 5).

Using the up/down arrows you may select the appropriate

number of decimal places. For this example select

1

and

touch

ENTER

.

10.