Appendix B – Configuring a 4-20 mA input to equal 0 to 150 gpm

Page 7 of 7

The photo below shows the proper connectivity for a 4-20 mA signal. To reduce ambient noise, a

properly shielded cable should be used. A 50 ohm precision resistor must be placed across the +

and – terminals in parallel with the input signal wires. Also, a jumper must be made between the –

and Cterminals (refer to Figure 2-7 in Chapter 2).

30

.

Attach cable
shield to
chassis
ground.

Place 50 ohm
resistor across
input + and –.

Link – and C
terminals.