AppendixA – Configuring a 1-5 Vdc input for a 0-250 psig pressure transducer

Page 6 of 6

You will now be back at the scale setup menu. Use the up/

down arrow keys to select

Scale units

and touch

ENTER

.

The alphanumeric keypad will be displayed. This is what

will be displayed as engineering units in the trend mode

only. For this example enter PSIG and touch

ENTER

.

Touch

EXIT

several times until you are completely out of all

menus.

The 0-250 scale complete with INLET and PSIG should be displayed on the recorder. Use the

VIEW button to select a particular display to verify your work.

26.

You will now be prompted with

hi

(some #). Enter the

high range of your scale range. For this example

(0-250 psig) enter

250.00

and touch

ENTER.