Appendix D – Configuring the Totalizer

Page 5 of 5

Use the up/down arrow keys to select

Low cutoff

and touch

ENTER

. You will be prompted with

cut

0.0

. This

feature allows you to enter a minimum flow rate at which the

totalizer should cut out and stop totalizing. This is for

transmitters that become very inaccurate at low flow rates.

Since ours is an open channel meter, we will not program a

low cutoff. Leave it set at

0.0

and touch

ENTER

.

21.

You should now be back in the menu beginning with

Point

tag

. Use the up/down arrow keys to select

Chart scale

and

touch

ENTER

. You will be prompted with

chart scl= A.

Use the up/down arrow keys to select

A

and touch

ENTER

.

Note

: Since the range of the flow meter is 0-50 MGD and

we will only be totalizing for a maximum of one day, the

totalizer will not exceed 50 so we can use the same scale.

If we were totalizing over long periods of time, we would

have to put in an appropriate scale for the totalizer channel.

Touch

EXIT

. You will be prompted

keep setup?

. Touch

YES

and you will be returned to the main program menu.

Touch

EXIT

several times until you are completely out of all

menus.

You have now successfully configured a totalization

channel! Use the

VIEW

button to select a particular display

to verify your work.

23.

22.

24.

You will now be back at the Reset Control menu. Use the

up/down arrow keys to select

Reset print

and touch

ENTER

. You will be prompted with

print=NO*

. Touch the

YES

key then touch

ENTER

. This enables the Recorder to

post the totalizer reset information to the alarm/event page

which is where you would view your daily totals.
Touch

EXIT

to get back to the menu beginning with

Point

tag

.

20.