Appendix B – Configuring a 4-20 mA input to equal 0 to 150 gpm
Page 1 of 7
Begin configuration bytouching the
MENU
button in the
lower right hand corner of the screen. This will bring up the
Command button bar. Touch the
PROG
button to enter into
the main program menu.
The numbers
1-9
and letters
A-F
represent the 15 channels
that can be set up. Touch the number or letter that
represents the input or channel you wish to configure. For
this example use number
1
and touch
ENTER
.
Prog point
and
Constants
will appear. Using the up/down
arrow keys select
Prog point
and touch
ENTER
.
Once in the main program menu use the up/down arrow
keys to select
Points
and then touch
ENTER
.
1.
4.
3.
2.
Appendix B
Configuring a 4-20 mA input to equal 0 to 150 gpm