Page 5-19

Chapter 5 Programming

Programming Parameters - Once a point has been selected and defined as Calculated, the Calculation
Type Programming menu appears. Select the calculated point type using the UP (

↑) or DOWN (↓) Arrow

Keys to highlight “Hi peak”, “Lo peak”, “Time avg”, “Gated timer”, or “Totalize” and press ENTER. This will
bring up the Calculated Point Type programming menu.

Selecting Reset Control - Use the UP (

↑) or DOWN (↓) Arrow Keys to highlight “Reset control” in the

Calculated Point Type programming Menu and press ENTER. There are three options.

a. Event Reset

Event Reset allows Calculated Points to be reset upon some external event via the optional digital
inputs on the rear panel. When programming Event Reset, the Event Number is the digital input
number for that external event, 1, 2 or 3. Selecting 0 disables Event reset.

Programming Event Reset - Use the UP (

↑) or DOWN (↓) Arrow Keys to highlight “Event reset” in the

Reset Control Setup Menu and press ENTER. The display will read “event? X”. Use the UP (

↑) DOWN

(

↓) Arrow Keys to select the desired event input number and press ENTER. The display will return to

the “Event reset” prompt in the Reset Control Setup Menu.

b. Reset print

The program in the Recorder allows point reset data to be printed on the Alarm/Event Data Log, at the
time of the reset, or if enabled, be stored to disk (5.7.2). This option can be toggled ON or OFF for each
resettable point.

Programming Reset Print - From the Reset Control Setup Menu, use the UP (

↑) DOWN (↓) Arrow

Keys to highlight “Reset print” and press ENTER. The display will read either “print=YES” or “print=NO”.
Use the YES or NO Key to select either “print=YES” “print=NO” and press ENTER. The display will
return to “Reset print’ in the Reset Control Setup Menu.

c.

Auto Reset

When programming High Peak, Low Peak, Totalize, Time Average, and Gated Timer points, the system
allows an Auto Reset function. If Auto Reset is set up, the point being programmed will reset at
programmed intervals, from once a minute to once a month. The system will prompt for the Start Time
and Interval for which that point will reset.

NOTE: If Auto Reset is disabled, resettable points may only be reset manually.

NOTE: Moving Average, High Peak, and Low Peak points reset to the current value of the base point.

Totalize points reset to zero.

Selecting Auto Reset - From the Reset Control Setup Menu, use the UP (

↑) or DOWN (↓) Arrow

Keys to highlight “Auto reset” in the Reset Control Setup Menu and press ENTER. The display will
read either “Auto off”, “Daily”, “Weekly”, or “Monthly”.

Selecting Auto Off - Use the UP (

↑) or DOWN (↓) Arrow Keys to highlight “Auto off” and press

ENTER. The display will return to “Auto reset” in the Reset Control Setup Menu. Automatic reset of
the programmed point is now disabled.

c.1 Daily Auto Reset

Use the UP (

↑) or DOWN (↓) Arrow Keys to highlight “Daily” and press ENTER. The display will

read “start XX:XX”. The Start Time is entered in a 24-hour clock format in Hours (00 through 23)
and Minutes (00 through 59). This is the time the first reset will begin, after this the point will reset
at the “interval” rate.