Page 5-21

Chapter 5 Programming

c.2 Weekly Auto Reset

To reset the point once a week use the Weekly reset option. Use the UP (

↑) or DOWN (↓) Arrow

Keys to highlight “Weekly” and press ENTER. The display will read a day of the week, Monday -
Tuesday - Wednesday - Thursday - Friday - Saturday - or Sunday.

Selecting the Week Day - Use the UP (

↑) or DOWN (↓) Arrow Keys to select the desired day of

the week and press ENTER. The display will read “start XX:XX”.

Selecting Start Time - It the Start Time displayed is correct, press ENTER and the display
returns to the “Auto reset” prompt in the Reset Control Setup Menu. If the displayed time is not
correct, press NO and the display reads “str hrs

ÆXX

←”. Use the Numeric keypad to enter the

desired Start Hours. Up to 23 hours may be programmed. When the correct Start Hours are
displayed press ENTER and the display reads “str min

ÆXX

←”. Use the Numeric keypad to enter

the desired Start Minutes. Up to 59 minutes may be programmed. When the correct Start
Minutes are displayed, press ENTER and the display returns to “start XX:XX”. If the Start Time
displayed is correct, press ENTER and the display returns to the “Auto reset” prompt in the Reset
Control Setup Menu.

c.3 Monthly Auto Reset

To reset the point once a month use the Monthly reset option. Use the UP (

↑) or DOWN (↓) Arrow

Keys to highlight “Monthly” and press ENTER. The display reads “first day

ÎXXÍ”. Use the

Numeric keypad to enter the desired day of the month on which to reset. Up to 31 may be entered
in this block to represent the number of the day in the month. When the correct day of the month
number is displayed, press ENTER and the display reads “Start XX:XX”. If the Start Time displayed
is correct, press ENTER and the display returns to the “Auto reset” prompt in the Reset Control
Setup Menu.

Selecting Start Hours - If the displayed Start Time is not correct, press NO and the display reads
“str hrs

ÎXXÍ”. Use the Numeric keypad to enter the desired Start Hours. Up to 23 hours may

be programmed here. When the correct Start Hours is displayed, press ENTER and the display
reads “str mins

ÎXXÍ”.

Selecting Start Minutes - Use the Numeric keypad to enter the desired Start Minutes. Up to 59
minuets may be programmed here. When the correct Start Minutes is displayed, press ENTER
and the display reads “str mins

ÎXXÍ”. If the correct Start Time is displayed, press ENTER and

the display returns to the “Auto reset prompt in the Reset Control Setup Menu.

5.6.5.14 Time Period

The Time Period is the time base used to set the duration (time) of the moving window. The point average
is set for this period of time (a maximum 1440 minutes of time is possible) and then the first scan is
dropped off and a new scan is averaged in.

Programming Time Period - Use the UP (

↑) or DOWN (↓) Arrow Keys to highlight “Time period” and

press ENTER. The display reads “minutes

→XXXX←”. Use the UP (↑) or DOWN (↓) Arrow Keys to select

the digit and the LEFT (

←) or RIGHT (→) Arrow Keys to move to a position to enter the desired Time

Period. A maximum 1440 minutes (24 hours) may be entered. When the desired Time Period is displayed,
press ENTER and the display returns to “Time Period”.

5.6.5.15 Gate Control

Gate Control can be turned on, “Gate=YES”, or off, “Gate=NO”. If Gate Control is turned on, a base point
must be established. If Gate Control is turned off, this Point Range can be used as a timer for
calculations, etc.

Advertising