Appendix A – Configuring a 1-5 Vdc input for a 0-250 psig pressure transducer

Page 2 of 6

The menu containing types of inputs should now be

displayed. Use the up/down arrow keys to select

Linear

and

then touch

ENTER

.

The menu starting with

Point tag

will appear again. Using

the up/down arrow keys select

Input scale

and touch

ENTER

. A numeric keypad will appear with

lo

→ ←

displayed. This is the point that you enter the low range of

your input signal. For this example (1-5 Volts DC) enter

1.00

as the low range and touch

ENTER

.

An alphanumeric keypad will be displayed. This is where

you enter a word or phrase (up to 10 characters*) that

describes this particular point. There are multiple pages of

letters, numbers and symbols that can be used. Use the

PAGE

,

PAGEBK

and

SHIFT

keys to access different

characters. For this example enter the word

INLET

and

touch

ENTER

.

* Only 8 characters will be displayed on the screen although

all ten will be recorded and can be displayed using the

Companion Software

.

The menu displaying types of linear inputs should now

appear. (Selections may appear different from the screen

example to the left.) For this example use the up/down

arrow keys to select the

12.5V

(for 12.5Volt) range then

touch

ENTER

.

The menu starting with

Point tag

will appear. Using the up/

down arrow keys select

Point tag

and touch

ENTER

.

6.

9.

8.

7.

If you are configuring the Recorder for the first time, a menu

having

Setup pt

,

Copy pt

and

Restore pt

will appear. If

you are changing a point that you have already configured,

the menu will have

Modify pt

and

Delete pt

. Depending on

which menu appears, use the up/down arrow keys to select

Setup pt

or

Modify pt

and then touch

ENTER

.

5.