Configuration and Activation 5-17

Return to Normal Enter the pressure depth reading at or

below which you want the FlowAlert to terminate alarming
conditions corresponding to a high depth alarm.

Depth Alarms – High High Edit the device to ensure the
FlowAlert initiates a high high depth alarm when a pressure
depth reading reaches or a exceeds a specified depth in the
following way:

Enable Select this checkbox to activate the high high

depth alarm options.

Trigger Enter the pressure depth reading at or above

which you want the FlowAlert to initiate a high high depth
alarm. ADS recommends that this value be at least 2
inches greater than the value entered for the high depth
trigger when it is in use.

Return to Normal Enter the pressure depth reading at or

below which you want the FlowAlert to terminate alarming
conditions corresponding to a high high depth alarm.

Depth Alarms – Low Edit the device to ensure the
FlowAlert initiates a low depth alarm when a pressure depth
reading reaches or falls below a specified depth in the
following way:

Enable Select this checkbox to activate the low depth

alarm options.

Trigger Enter the pressure depth reading at or below

which you want the FlowAlert to initiate a low depth
alarm.

Return to Normal Enter the pressure depth reading at or

above which you want the FlowAlert to terminate alarming
conditions corresponding to a low depth alarm.