AERCO RECON 1000 User Manual

Page 101

Advertising
background image

RECON Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 7 – TROUBLESHOOTING GUIDE

OMM-0103_0A

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

Page 101 of 178

GF-147

Phone: 800-526-0288 PRI:

10/28/2014

TABLE 7-1: WATER HEATER TROUBLESHOOTING

FAULT INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

AIRFLOW FAULT
DURING IGNITION

1.

Blower stopped running due to
thermal or current overload

2.

Blocked Blower inlet or inlet ductwork

3.

Blocked Blower proof switch

4.

Blocked blocked-air inlet switch

5.

Defective Blower proof switch


6.

Defective blocked-air inlet switch


7.

Loose temperature to AUX connection
in I/O Box

8.

Defective temperature sensor

9.

Loose wire connection between the 0-
10V signal from I/O box to the Blower
Motor input

10.

Defective I/O box

11.

Wrong 0-10V output selection on the

control box

12.

Defective Air-Fuel Valve

potentiometer

1.

Check combustion blower for signs of excessive heat or high
current drain that may trip thermal or current overload devices.

2.

Inspect the inlet to the combustion blower including any ductwork
leading up to the combustion blower for signs of blockage.

3.

Remove the Blower proof switch and inspect for signs of
blockage, clean or replace as necessary.

4.

Remove the blocked-air inlet switch and inspect for signs of
blockage, clean or replace as necessary.

5.

Measure the Blower proof switch for continuity with the
combustion blower running. If there is an erratic resistance
reading or the resistance reading is greater than zero ohms,
replace the switch.

6.

Measure the blocked-air inlet switch for continuity with the
combustion blower running. If there is an erratic resistance
reading or the resistance reading is greater than zero ohms,
replace the switch.

7.

Check the actual inlet air temperature and measure voltage at
AUX input in the I/O Box. Verify that the voltage conforms to the
values shown in the tabular listing provided in Appendix C.

8.

Refer to CORRECTIVE ACTION 7 and verify that the voltage
conforms to the values shown in Appendix C.

9.

Check wire connection from I/O Box 0-10V signal to the Blower
Motor.

10.

Measure voltage at the I/O box 0-10V output. A voltage of 8.2V

equates to a 100% open valve position.

11.

Check the Analog Out option on the C-More Configuration

Menu. Valve Position 0-10V should be selected.

12.

Check Air/Fuel Valve position at 0%, 50% and 100% open

positions. The positions on the VALVE POSITION bargraph
should match the dial readings on the Air/Fuel Valve dial.