AERCO RECON 1000 User Manual

Page 109

Advertising
background image

RECON Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 7 – TROUBLESHOOTING GUIDE

OMM-0103_0A

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

Page 109 of 178

GF-147

Phone: 800-526-0288 PRI:

10/28/2014

TABLE 7-1: WATER HEATER TROUBLESHOOTING –

Continued

FAULT INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

RESIDUAL
FLAME

1.

SSOV not fully closed.

2.

Defective Flame Detector

1.

Check open/close indicator window of Safety Shut-Off Valve
(SSOV) and ensure that the SSOV is fully closed. If not fully
closed, replace the valve and or actuator.
Close the 1 1/4” Gas Shut-Off Valve downstream of SSOV (Figure
7-1). Install a manometer or gauge at the leak detection port
between the SSOV and Gas Shut Off Valve. If a gas pressure
reading is observed replace the SSOV Valve and/or Actuator.

2.

Replace Flame Detector.

SSOV FAULT DURING
PURGE

See SSOV SWITCH OPEN

SSOV FAULT
DURING RUN

SSOV switch closed for 15 seconds
during run.

Replace or adjust microswitch in SSOV actuator. If fault persists,
replace actuator.

SSOV RELAY
FAILURE

1.

SSOV relay failed on IGST board.

2.

Floating Neutral.


3.

Hot and Neutral reversed at SSOV.

1.

Press CLEAR button and restart unit. If fault persists, replace
Ignition/Stepper (IGST) Board.

2.

The Neutral and Earth Ground are not connected at the source
and therefore there is a voltage measured between the two. This
measurement should be near zero or no more than a few
millivolts.

3.

Check SSOV power wiring.

SSOV
SWITCH OPEN

1.

Actuator not allowing for full closure
of gas valve

2.

SSOV powered when it should not
be

3.

Defective Switch or Actuator

4.

Incorrectly wired switch.

1.

Observe operation of the Safety Shut-Off Valve (SSOV) through
indicator on the Valve actuator and ensure that the valve is fully
and not partially closing.

2.

If the SSOV never closes, it may be powered continuously. Close
the gas supply and remove power from the unit. Refer fault to
qualified service personnel.

3.

Remove the electrical cover from the SSOV and check switch
continuity. If the switch does not show continuity with the gas
valve closed, either adjust or replace the switch or actuator.

4.

Ensure that the SSOV Proof of Closure switch is correctly wired.

Advertising
This manual is related to the following products: