RECON Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 6 – MAINTENANCE

OMM-0103_0A

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

Page 85 of 178

GF-147

Phone: 800-526-0288 PRI:

10/28/2014

Fireside Inspection – Continued

Figure

6-4: Removing the Blower Side Air Intake, Burner Assembly, and Gaskets


Figure

6-5: Removing the Exhaust Manifold

EXHAUST
MANIFOLD

INTAKE MANIFOLD

5/16-18 HEX NUTS (6 EACH)

CONDENSATE

SHIELD

STEP 13: REMOVE SIDE
NUTS & WASHERS (2 each)

STEP 13: LOOSEN,
BUT DO NOT REMOVE
FRONT NUT/WASHERS

STEP 12: UNSCREW AND
REMOVE EXHAUST
TEMPERATURE SENSOR

EXHAUST MANIFOLD

NOTE

Support the intake manifold as it is carefully lowered from
the blower plenum and heat exchanger.

MANIFOLD-TO-HEAT
EXCHANGER GASKET
(P/N GP-122537)
PLUS RTV SILICONE

BURNER MOUNTING PLATE

BURNER FLANGE GASKET (P/N GP-18899)

BLOWER

MANIFOLD

GASKET

(P/N 81136)

10-22 x 3/8” BURNER MOUNTING SCREWS

BURNER FLANGE GASKET (P/N GP-18899)
SHIELD GASKET (P/N 81197)