RECON Water Heaters Installation, Operation & Maintenance Manual

CHAPTER 6 – MAINTENANCE

Page 80 of 178

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

OMM-0103_0A

PRI: 10/28/2014

Phone: 800-526-0288

GF-147

6.2 IGNITER-INJECTOR

The ignition system’s igniter-injector (kit P/N 58023) is located on the burner plate on the
underside of the heat exchanger. In addition to providing the ignition spark required to light the
burner, the igniter-injector also contains a gas injector tube which connects to the ignition
assembly. Figure 6-1 indicates the location of the igniter-injector assembly, the flame detector,
and other related components. Note that the cables normally connected to the igniter-injector and
flame detector terminals are not shown in Figure 6-1 for clarity.

Figure 6-1: Blower-Side intake Manifold with Igniter-Injector & Flame Detector

Igniter-Injector Inspection and Replacement

1. Set the ON/OFF switch on the control panel, to the OFF position. Disconnect AC power from

the unit.

2. Remove the panels from the unit to reveal the ignition assembly, which is at the bottom of the

heat exchanger. See Figure 6-1 for component identification.

3. Disconnect the cable from the igniter-injector.

4. Refer to Figure 6-1. Disconnect the compression nut securing the gas injector tube of the

igniter-injector to the elbow of the ignition assembly. Disconnect the ignition assembly from
the igniter-injector.

5. Next, loosen and remove the igniter-injector from the burner plate.

6. Check the igniter-injector for evidence of erosion or carbon build-up. If there is evidence of

substantial erosion or carbon build-up, the igniter-injector should be replaced. If carbon build-
up is present, clean the component using fine emery cloth. Repeated carbon build-up is an
indication that the combustion settings of the unit should be checked. Refer to Chapter 4 for
combustion calibration procedures.

FLAME

DETECTOR

TERMINAL

INTAKE

MANIFOLD

IGNITER TERMINAL

IGNITION ASSEMBLY
SOLENOID VALVE

OBSERVATION PORT

GAS INJECTOR TUBE

COMPRESSION ELBOW & NUT

FLAME

DETECTOR

GASKET

FLEX GAS
HOSE NIPPLE

FLAME DETECTOR MOUNTING STAND-OFFS

CLOCKING WASHERS (1 TO 3 EA.)