AERCO RECON 1000 User Manual

Page 139

Advertising
background image

RECON Water Heaters Installation, Operation & Maintenance Manual

APPENDIX A – RECON MENU ITEM DESCRIPTIONS

OMM-0103_0A

AERCO International, Inc.

 100 Oritani Dr.  Blauvelt, NY 10913

Page 139 of 178

GF-147

Phone: 800-526-0288 PRI:

10/28/2014

Table A-4: Tuning Menu Item Descriptions

Table A-4: TUNING MENU ITEM DESCRIPTIONS

See section 3-7 for a range of choices and the default values.

MENU LEVEL & OPTION

DESCRIPTION

1

Prop Band

Generates a valve position based on the error that exists
between the setpoint temperature and the actual outlet
temperature. If the actual error is less than the proportional
band setting (1 to 120°F), the valve position will be less than
100%. If the error is equal to or greater than the proportional
band setting, the valve position will be 8%.

2

Integral Gain

This sets the fraction of the output, due to setpoint error, to add
or subtract from the output each minute to move towards the
setpoint. Gain is adjustable from 0.00 to 10.00

3

Derivative Time

This value (0.0 to 20.0 min.) responds to the rate of change of
the setpoint error. This is the time that this action advances the
output.

4

Min Load Adj

Setting is adjustable from -50°F to +50°F. It adjusts the output
by adding an offset to the breakpoint chart at minimum flow.
This is used to fine tune Feed-Forward (FFWD) output at low
flow levels.

5

Max Load Adj

Setting is adjustable from -50°F to +50°F. It adjusts the output
by changing the scaling of the breakpoint chart at maximum
flow.

6

FFWD Temp

Displays the Feed-Forward temperature.

7

Outlet Feedback

Used to Enable or Disable feedback. Disable this function for
Feed-Forward control only.

8

Feedback Gain

Adjustable from 0.01 to 1.00 (See NOTE below)

9

Thru

19

Breakpoint at 100%
Thru
Breakpoint at 0%

Allows breakpoint temperature settings (30°F to 240°F) to be
entered for 100% to 0% in 10% increments. See Appendix D
for default values.

20

FDback Start Pos

Start of Feedback Position

21

Fdback End Pos

End of Feedback Position

22

Max Feedback

Max Feedback

23

Fdback Value

Monitor Feedback Value